Winding Relay

Overview

  • Easy to Operate
  • Higher accurancy
  • Output relay contact used in 1 C/O
  • Sencing motor winding themperature though PTC thermistors
  • Winding Overheating, sensor short, sensor open fault indicate

Technical Specification

Supply voltage 230V AC
415V AC
Trip time delay less than 2 sec
Resetting Automatic
Indication Healthy and trip
Contact rating 6 Amp
Output Relay contact 1 C/O
Enclosure PVC box
Weight 0.336 gms
Dimension (mm)  
-Dimension (HXWXD) (113 X 78 X 51)
-Base mounting Yes
Trip Setting  
-Thermistor Sensor healthy 40 ohms-4 k ohms
-Thermistor Sensor trip 4.1 k ohms-5.5 k ohms
-Thermistor Sensor open 5.6 k ohms & above
-Thermistor Sensor short 40 ohms & below

Application